Metal Clad Switchgear for Substation Busbars
Serving as the primary control and protection assembly in 10kV to 40.5kV distribution networks, this switchgear manages step-up incoming feeders, power transformer circuits, and distribution cables. Installed in municipal substations, solar collector stations, and heavy industrial facilities, this High Voltage Distribution Switchgear uses a fully compartmentalized metal-clad structure to contain internal faults and protect operators.

Four Compartment Partition and Five Safety Interlocks
The enclosure is partitioned by aluzinc-coated steel sheets into four isolated compartments: Busbar Compartment, Circuit Breaker Compartment, Cable Compartment, and Low Voltage Relay Compartment. Each high-voltage chamber incorporates an independent pressure relief flap that vents upward. Integrated mechanical interlocks prevent racking the breaker under load, closing earth switches onto live busbars, or opening compartment doors while energized.

Product Specifications
|
Parameter |
Value |
|
Series |
KYN28 / KYN61 Series |
|
Rated Voltage |
10kV, 40.5kV |
|
Structural Form |
Metal-Clad Withdrawable Truck Type |
|
Rated Current |
1250A - 3150A |
|
Short-circuit Withstand Current |
25kA - 31.5kA |
|
Primary Switching Device |
Vacuum Circuit Breaker |
Precision Sheet Metal Forming And Truck Interchange
Manufactured using high-precision CNC punch presses and automated press brakes, dimensional tolerances are closely controlled to ensure smooth withdrawable truck operation. Circuit breaker trucks of identical electrical ratings can be interchanged freely between different cubicles without binding or contact misalignment.
Insulation Withstand Testing And Export Loading
Every High Voltage Distribution Switchgear cubicle completes power-frequency overvoltage testing, secondary relay operational simulations, and contact resistance checks. For export transport, circuit breaker trucks are racked into the test position and mechanically locked, and panels are crated in reinforced wooden cases for container stowage.
FAQ
Q: Can the switchgear accommodate digital microcomputer protection relays?
A: Yes. Low-voltage doors are pre-cut and pre-wired to integrate specified digital protection relays and multifunction power meters, communicating via Modbus, IEC 60870-5-104, or IEC 61850 protocols.
Q: Are top busbar bridge entries and bottom cable entries supported?
A: Yes. The cable compartment offers generous clearance for bottom heat-shrink cable terminations, and top-entry busbar trunking enclosures can be supplied for transformer connections.
Hot Tags: high voltage distribution switchgear, China high voltage distribution switchgear manufacturers, suppliers, factory, high voltage metal clad switchgear, low voltage switchgear, medium voltage control panel, switchgear compartment, switchgear interlock system, switchgear protection relay